HVAC / Engineering tools
Heat exchanger LMTD & UA
Evaluate terminal temperature differences and conductance for parallel or counterflow.
Method & assumptions
ΔTₗₘ = (ΔT₁ − ΔT₂) / ln(ΔT₁/ΔT₂)
UA = Q̇ / ΔTₗₘ
For counterflow: ΔT₁ = Th,in − Tc,out and ΔT₂ = Th,out − Tc,in. For parallel flow: ΔT₁ = Th,in − Tc,in and ΔT₂ = Th,out − Tc,out. Equal terminal differences use their common value.
Assumes steady heat transfer, constant overall U, no external heat loss, and correction factor F = 1. Both streams must remain single-phase with monotonic temperature change. Multipass and crossflow arrangements need a correction factor. Independently check that both stream energy balances match the entered duty.
Build confidence in the result.
Record assumptions and compare against independent evidence using the simulation validation guide.
Get future tools and technical issues →