Heat exchanger case comparison

Compare two operating cases using both stream energy balances, LMTD, UA, and pressure drop.

Case A

Case B

Case comparison

QuantityCase ACase B
Hot-side heat loss12.54 kW13.376 kW
Cold-side heat gain12.54 kW13.376 kW
Balance difference0%0%
Mean duty (provisional if imbalanced)12.54 kW13.376 kW
LMTD26.472 K25.567 K
Inferred UA473.714 W/K523.182 W/K
Minimum terminal approach25 K24 K
Hot-side Δp15 kPa22 kPa
Cold-side Δp12 kPa18 kPa

Method & limits

Each stream duty uses ṁ cₚ ΔT. The displayed duty averages hot and cold estimates to make an imbalance visible; it is provisional when they disagree. LMTD uses the selected flow arrangement and UA = mean duty / LMTD. Pressure drops are inputs for comparison, not predictions.

Use consistent boundaries and flow rates for a fair comparison. Phase change, heat loss to ambient, variable properties, fouling, and crossflow or multipass correction are outside this first-pass method.

Read the heat exchanger guide →