Thermal systems / Field guide 02
A first-pass heat exchanger check
Before estimating area, make the proposed inlet and outlet states agree with conservation of energy. Then check the temperature driving force. A plausible UA from inconsistent temperatures is still a bad design input.
1. Close both sides of the energy balance
For a single-phase stream with approximately constant heat capacity, use Q = ṁ cp ΔT. For a refrigerant changing phase or a fluid with strongly varying properties, use measured or modeled enthalpies: Q = ṁ(hout − hin), with the sign chosen consistently for each stream.
Compare hot-side heat loss with cold-side heat gain. A mismatch can come from sensors, property data, heat loss to ambient, or a wrong flow measurement. Do not silently average a large mismatch away.
2. Compute the counterflow driving force
For counterflow, define ΔT1 = Th,in − Tc,out and ΔT2 = Th,out − Tc,in. Both must be positive for this simple sensible-heat example. Calculate ΔTlm = (ΔT1 − ΔT2)/ln(ΔT1/ΔT2); if they are equal, use their common value. The first-pass conductance is UA = Q/ΔTlm. Crossflow and multipass layouts need an appropriate correction or another exchanger method.
Worked example
Consider hot water at 0.20 kg/s cooling from 60 to 45 °C and cold water at 0.25 kg/s warming from 20 to 32 °C. Using cp = 4,180 J/(kg·K) on both sides gives 12.54 kW from each energy balance. The counterflow end differences are 28 and 25 K, so ΔTlm ≈ 26.47 K and UA ≈ 474 W/K. These are illustrative inputs, not a component rating.
3. Test the limits before selecting hardware
Check minimum approach temperature, pressure drop at both flow rates, fouling allowance, flow regime, and off-design states. A very small approach can demand much more area or become impossible once control and property variation are included. Record which side defines the area basis when converting UA into U and A.
Try the heat exchanger tool for a quick calculation and carry the assumptions into your worksheet.
Compare two measured operating cases with the exchanger comparison tool.